Technical Data

Properties Test Methods Typical Values
Tensile Strength (MPa) ASTM D 2671 ≥ 13
Tensile (after thermal aging MPa) ASTM D 2671/120°C, 168Hrs ≥ 10
Ultimate Elongation (%) ASTM D 2671 ≥ 300
Ultimate Elongation (after thermal aging %) ASTM D 2671/120°C, 168Hrs  ≥ 250
Dielectric Strength (kV/mm) IEC 60243 ≥ 15
≥ 20 (6core)
Volume Resistivity (Ω,cm) IEC 60093 1014
Water absorption (%) ISO 62 ≤1%
Operating Temperature (°C) -55 to 110
Minimum Shrink Temp. (°C) 110
Min. Full Shrink Temp. (°C) 130

 

Description

ALB Cable breakout boots (inner coated with hot melt adhesive) are manufactured from crosslinked polyolefin & have been designed to offer excellent sealing & insulating properties when used on a cable crutch.

 

Features

  •  Excellent UV & environmental resistance
  • Adhesive lining offers reliable sealing properties
  • Excellent electrical & mechanical properties
  • Abrasion resistance
  • Available in 2, 3, 4, 5 & 6 cores

Dimensions

Size (mm) D (body) I – Large Finger I2 – Small Finger Length ±10% Recovered Wall ±20%
Supplied Recovered Supplied Recovered Supplied Recovered L-Total F-Finger DW (Body)
lw
(Large Finger)
lw2
(Small Finger)
2 Cores Cable Breakout
ALB22/8 – 2 22 8 9 3.5 55 18 2.2 1.8
ALB30/12 – 2 30 12 14 4.5 93 23 2.6 2.2
ALB40/16 – 2 40 16 15 5 125 35 2.1 2.1
ALB60/23 – 2 60 23 25 7.5 118 29 2.6 2.6
ALB60/23L – 2 60 23 25 7.5 155 45 2.6 2.6
ALB100/42 – 2 100 42 30 9 155 55 3.1 3.1
ALB150/75 – 2 150 75 20 6 170 64 3.8 3.8
3 Cores Cable Breakout
ALB38/16 – 3 38 17 14 4.5 98 23 2.7 2.7
ALB60/24 – 3 60 25 25 8 165 50 3 2.5
ALB80/36 – 3 80 38 35 11 185 55 3.5 3.5
ALB110/48 – 3 110 50 46 17.5 250 65 4 4
ALB125/57 – 3 125 57 55 20 260 75 4 4
ALB140/70 – 3 140 70 62 26 280 75 4 4
ALB170/77 – 3 170 77 75 28 280 80 4 4
4 Cores Cable Breakout
ALB4015 – 4 42 15 14 3.5 105 26 2.2 2
ALB55/21 – 4 55 21 20 5 150 40 3.1 2.6
ALB65/26 – 4 65 26 26 7 175 45 3.3 2.9
ALB75/26 – 4 75 26 28 7 175 45 3.3 2.9
ALB82/37 – 4 82 37 30 9 190 60 4 3
ALB90/37 – 4 90 37 32 9 190 60 4 3
ALB100/47 – 4 102 47 38 12 198 58 4 3
ALB125/52 – 4 130 52 52 15 240 75 4 4
ALB160/70 – 4 160 70 64 19 260 75 4 4
5 Cores Cable Breakout
ALB40/19 – 5 40 19 13 4 98 25 2.5 2
ALB55/24 – 5 55 24 18 5 155 40 3.2 2.6
ALB80/33 – 5 80 33 26 8 175 53 3 2.6
ALB100/42 – 5 100 42 34 10 190 60 3 3
6 Cores Cable Breakout
ALB86/40 – 6 83 41 31 12 20 8 215 60 3.3 2.9 2.6
ALB130/55 – 6 130 55 53 17 30 12 220 70 3.6 3.1 2.6

 